1、 Performance Overview


Drive intrinsically safe low-power equipment in hazardous areas by controlling the output through dry contacts, collector open circuit signals, or logic level signals. Intrinsic safety equipment such as solenoid valves, sound and light alarms, etc.


Three party isolation of input, output, and power supply terminals.


switch output isolated safety barrier

2、 Technical parameters


Explosion proof grade: [Exia] IIC


Safe zone allows input signal: dry contact collector open circuit signal


Logic level: When 5V~30V, it indicates "on" and supplies power to the on-site equipment


When 0V~1V, it means "off" and stops supplying power to the on-site equipment


Output signal to danger zone: digital output drives solenoid valve or alarm


High output voltage: 22V


Small output voltage: 12V


Current limit 45mA


Dielectric strength: ≥ 2500V AC (between input/output/power supply, leakage current 1mA, testing time 1min)


Insulation resistance: ≥ 100M Ω (between input/output/power supply)


Electromagnetic compatibility: EMC complies with IEC61000-4


Certification parameters of National Quality Supervision and Inspection Center for Instrumentation and Electrical Products (CQST): between terminals 9 and 10; 11. Between 12 terminals: Um=250V AC/DC


Uo=25.2V,Io=109mA,Po=687mW


ⅡC           ⅡB         ⅡA


Co        0.074μF       0.57μF      2.03μF


Lo        2.1mH         6.3mH      16.8mH


Power supply: DC 18-32V (typical value 24V DC)


Power consumption: 2.4W


Panel indicator light


PWR: Power indicator light (green). Always on during work.


CH1, CH2: Input signal status indicator light (red). The indicator light of the corresponding channel lights up when outputting the signal.


Usage environment


Working environment temperature: -20 ℃ to+60 ℃


Allowable relative humidity at work: 10% RH to 90% RH (40 ℃)


Allowable atmospheric pressure during work: 80kPa~106kPa


Allowable ambient temperature during storage and transportation: -40 ℃ to+80 ℃


    


MESEJ DALAM TALIAN

*Subjek:
*E-mail:
Phone:
syarikat:
*Kode Verifikasi:

PRODUK BERKAITAN

Contact Us

Company Address:

Building 5 and 11, Fuzhou IoT Industrial Park, 

No. 12 Xingye West Road, Mawei District, 

Fuzhou City, Fujian Province, China

Market Cooperation:

Manager Guo: 13959146212


Hak Cipta © 2025 Fujian Aotai Automation Equipment Co., Ltd

Laman web ini menggunakan kuki untuk memastikan anda mendapat pengalaman terbaik di laman web kami.

Terima menolak